Watermist - Standards and Applications16 July 2009The near completion of two ‘draft for development' standards marks another step towards better specified watermist systems for a wide range of applications. Bob Whiteley brings you up to speed on their development. The use of watermist fire protection has been evolving since the 1990s, but the lack of robust standards for land based applications has been seen as barrier to general acceptance of this technology. Although there is a European standard for watermist systems, it became clear that it was limited in scope and has been published as an advisory document only. The members of the main BSI fire protection systems committee, FSH/18, were concerned that the work on the European standard would not meet UK needs in a timely fashion. In anticipation of this, a series of joint watermist working groups were formed to prepare separate standards covering commercial and industrial applications, and domestic and residential applications. In view of the rapid pace of development in this technology, it was deemed appropriate for these standards to be DDs – Drafts for Development – in effect, provisional standards. In this form they can be created and published quickly and would enable experience to be gained over their two year life span, before they would be reviewed and considered for adopting as full British Standards. Three working groups were formed:
Membership of the joint working groups was provided by knowledgeable and interested parties from the Fire Industry Association, British Automatic Fire Sprinkler Association, the Fire Protection Association, Factory Mutual, Loss Prevention Certification Board and insurers. The members assembled the best available information on watermist and existing mist system design and test standards as the basis for the UK standards. What is watermist? There are various mechanisms for generating small water droplets at high momentum which are well documented. Some nozzles use a separate gas supply to each nozzle to atomise the water. Some rely upon an external deflector plate to break up the water stream into fine droplets. Other nozzles incorporate a number of small sub-nozzles with very small orifice plates in them. Lastly there are nozzles which contain an internal ‘swirl chamber' delivering a rotating sheet of water which fractures into very small droplets. As with other water based fire systems, watermist nozzles may be ‘closed' by thermally activated frangible elements, or they may be ‘open' nozzles. Watermist systems and equipment exist at operating pressures from 5-6 bar to over 200 bar to suit the component technologies being used. These considerations, however, have no bearing on the watermist standards which are being developed, as these standards focus on the performance requirements of any and all mist systems against defined fire scenarios. A particular feature of all watermist systems is their highly efficient use of water, which results in low water usage compared with other water based fire protection systems. In addition they provide excellent cooling of the fire and its surroundings, which can provide increased safety for firefighters and other personnel. Where is watermist used?
However, the lack of common and consistent test protocols makes it difficult to establish the robustness of the test performance claims being made. Depending on the application, watermist may provide fire suppression (complete fire knockdown but no extinguishment) for fires involving ordinary combustibles, but for flammable liquid fires, it may be engineered for extinguishment as well as for suppression. When considering watermist, therefore, it is important to understand what each particular system can provide. The work behind DD 8458 – Code of Practice for the Design and Installation of Watermist Fire Suppression Systems for Residential and Domestic Occupancies – centres around a series of fire tests in an 8m x 4m room with both corner and centre room fires, with and without a through airflow. The watermist must suppress the fire for at least 10 minutes for domestic applications and 30 minutes for residential ones. It must also limit temperatures within the enclosure as well as preventing fire spread. For each manufacturer the tests will establish a set of design parameters giving:
System design criteria for domestic and residential applications require protection of all parts of a dwelling excluding bathrooms (<5m2), cupboards, non-communicating buildings such as garages, and crawl space. Pipework must be hydraulically calculated and may be copper, galvanised steel, stainless steel or fire rated PVC, with all systems hydrotested to 1.5 times their working pressure for one hour on completion. The water supplies for watermist systems can be provided by either dedicated cylinders or from a pump and tank system. These must be able to supply the required flow and pressure for all nozzles to operate in any given room. Commercial and industrial systems For extinguishing systems, the water supplies are required to operate for twice the time needed during testing to extinguish the fires and prevent re-ignition with the maximum number of nozzles operating. For suppression systems, the water supplies must run for at least 30 minutes with twice the number of nozzles operating than these which operated during the tests. Thus a 100% safety factor has been incorporated into the water supply and hydraulic provisions of the standard. Where pump suction storage tanks are used, their capacity should not be less than 30% of the total water requirement along with sufficient infill capacity. As with domestic and residential watermist systems, the water supplies may be from dedicated cylinders or pump and tank. Again, systems must be hydraulically calculated and corrosion resistant piping used. Which standard? Both DD 8458 and DD 8489 are in their final stages of drafting with the Joint Working Groups liaising with BSI editors to finalise the text. On completion, the drafts then have to be approved by the main BSI fire systems committee – FSH/18 – so that once approved, these will be published by BSI. It is envisaged that this will occur later this year. The joint working groups will then begin work on the component requirements (for which considerable data already exists), and on an office fire test protocol. It is envisaged that other test protocols will be added in response to commercial and industry requirements. Bob Whiteley C.Eng.; M.I.Mech.E.;M.I.Fire E.; B.Tech(Hons) is engineering & standards manager at Tyco Fire & Integrated Solutions and chair of the BSI Watermist Joint Working Group. |